Digital PV Solution for Optimal LCOE.
Max DC voltage: 1500 V
Max AC apparent power: 185,000 VA
9 MPPTs for versatile adaptions to different layouts
18 strings intelligent monitoring and fast trouble-shooting
Max. efficiency 99.03% , EU efficiency
Technical Specifications
|
SUN2000-185KTL-H1
|
||
Efficiency
|
|||
Max.Efficiency
|
99.03 %
|
||
Input
|
|||
Max. input voltage
|
1500 V
|
||
Max. Current per MPPT
|
26 A
|
||
Max. Short Circuit Current per MPPT
|
40 A
|
||
Start Voltage
|
550 V
|
||
MPPT Operating Voltage Range
|
500V ~ 1500V
|
||
Nominal Input Voltage
|
1080 V
|
||
Number of Inputs
|
18
|
||
Number of MPP Trackers
|
9
|
||
Output
|
|||
Nominal AC Active Power
|
185 KW@25℃, 175KW@40℃
|
||
Max. AC Apparent Power
|
185 KVA
|
||
Max. AC Active Power (cosφ=1)
|
185 KW
|
||
Nominal Output Voltage
|
800 V, 3W+PE
|
||
Rated AC Grid Frequency
|
50/60 Hz
|
||
Nominal Output Current
|
134.9A@25℃, 126.3A@40℃
|
||
Max. Output Current
|
134.9 A
|
||
Adjustable Power Factor Range
|
0.8LG...0.8LD
|
||
Max. Total Harmonic Distortion
|
<3%
|
||
Protection
|
|||
Input-side Disconnection Device
|
Yes
|
||
Anti-islanding Protection
|
Yes
|
||
AC Over-current Protection
|
Yes
|
||
DC Reverse-polarity Protection
|
Yes
|
||
PV-array String Fault Monitoring
|
Yes
|
||
DC surge protection
|
Yes
|
||
AC surge protection
|
Yes
|
||
DC Insulation Resistance Detection
|
Yes
|
||
Residual Current Monitoring Unit
|
Yes
|
||
General
|
|||
Dimensions ( W*H*D)
|
1035*700*365 mm
|
||
Weight (with mounting plate)
|
84 Kg
|
||
Operating Temperature Range
|
-25~60 ℃
|
||
Cooling Method
|
Smart Air Cooling
|
||
Max. operating altitude
|
4000 m
|
||
Relative Humidity
|
0~100%
|
||
DC Connector
|
Staubli EVO2
|
||
AC Connector
|
Waterproof Connector + OT/DT Terminal
|
||
Protection Degree
|
IP66
|
||
Topology
|
Transformerless
|
||
Standard Compliance
|
|||
Grid connection standards
|
EN 62109-1/-2, IEC 62109-1/-2,
|